2020 Fire Protection

2020 Fire Protection Fire Protection Experts. Less Headaches! We're a full-service Fire Protection company in Sydney. We apply 20/20 vision to help keep people safe!

As of 13th February 2026, AS1851–2012 became mandatory across NSW, bringing a sharper focus on compliance, accountabilit...
02/09/2026

As of 13th February 2026, AS1851–2012 became mandatory across NSW, bringing
a sharper focus on compliance, accountability and what it truly means to be
a ‘Competent Person’ in fire protection.

Join our free webinar on Tuesday 15th of September | 2pm - 3pm

https://2020fireprotection.com.au/as1851-competent-person-webinar/?v=1

As of 13 February 2026, AS1851–2012 has become mandatory across NSW—bringing a sharper focus on compliance, accountability, and what it truly means to be a ‘Competent Person’ in fire protection. For many organisations, this isn’t just a regulatory update—it’s a significant shift in how...

Please join us in congratulating Nigel Swanson on his promotion to Fire Service Technician Supervisor!Congratulations, N...
28/08/2026

Please join us in congratulating Nigel Swanson on his promotion to Fire Service Technician Supervisor!

Congratulations, Nigel — we're proud to have you on the team!

Want to know how to identify and reduce the risk around your Light Electric Vehicle (LEV)?  To read the full post, click...
26/08/2026

Want to know how to identify and reduce the risk around your Light Electric Vehicle (LEV)?

To read the full post, click the link below:

https://2020fireprotection.com.au/levs-lithium-ion-batteries-a-growing-risk/?v=1

Want to know how to identify and reduce the risk around your Light Electric Vehicle (LEV)? This week’s post details a safe use guide for owners, while discussing some of the emerging risks associated with the rapidly growing use of e-bikes and e-scooters.

Instead of our regular procedure, we have two winners this month!A big shoutout to Dean & Jai for demonstrating exceptio...
20/08/2026

Instead of our regular procedure, we have two winners this month!

A big shoutout to Dean & Jai for demonstrating exceptional
drive and initiative, maintaining momentum and seeking out additional work,
directly contributing to our overall team productivity and client satisfaction.

Congratulations!

We're excited to welcome Cameron as Senior Fire Service Technician and Accredited Practitioner (Fire Safety). Cameron is...
14/08/2026

We're excited to welcome Cameron as Senior Fire Service Technician and Accredited Practitioner (Fire Safety). Cameron is qualified in 24 measures, with more coming in the near future.

Welcome aboard, Cameron - glad to have you with us!

The Passive Team are on the tools delivering a fire-engineered passive fire solution that's as much about heritage as it...
11/08/2026

The Passive Team are on the tools delivering a fire-engineered passive fire solution that's as much about heritage as it is about safety.

Developed in collaboration with TBA Firefly and our Fire Engineers, this project strikes the perfect balance, preserving the building's heritage character while achieving the required fire compartmentation between floors.

Proud to be part of a team that doesn't just meet the brief but respects the history behind it.

During a routine maintenance visit and while completing the surrounding asset survey required under AS 1851-2012, we not...
07/08/2026

During a routine maintenance visit and while completing the surrounding asset survey required under AS 1851-2012, we noticed several electrical and fire cables hanging unusually low.
On closer inspection, we discovered the cables were close to a diesel fire pump exhaust. The radiant heat from the exhaust had gradually softened the cable and conduit, causing the cables to sag. Eventually, they came into contact with the hot exhaust pipe, resulting in the insulation melting onto the pipe and the cables being close to shorting.
This is a great example of why the surrounding asset surveys required under AS 1851-2012 are so important. While the fire pump itself was operating correctly and no faults had yet occurred due to the cables melting, the survey identified a potentially serious hazard that may have otherwise gone unnoticed and may have impacted other systems' reliability or safety if untreated.

Routine Service isn't just about inspecting the asset you're working on, it's about assessing the entire system, how it fits with the building and its surrounding environment. Taking the time to look beyond the obvious can prevent failures, improve reliability and ultimately keep people and property safe.

Proactive planning beats reactive panic every time.A few years ago, we identified minor intermittent faults on two of a ...
04/08/2026

Proactive planning beats reactive panic every time.

A few years ago, we identified minor intermittent faults on two of a client's fire pump system control panels. The panels were still working but the signs pointed to a bigger problem down the track. Without action, a complete failure was only a matter of time.

Instead of waiting for that failure to happen, we gave the client a quote three years in advance.

Why? Because we believe fire protection isn't just about fixing what's broken, it's about helping clients plan ahead, budget realistically and avoid being blindsided by urgent, costly repairs.

That early conversation meant our client could:
• Plan the works around their own timeline
• Budget for the upgrade without financial strain
• Complete the replacement in a controlled way, on their terms
• Avoid the disruption and higher costs of an unexpected failure

At 2020 Fire, we know every client's operational and financial situation is different. Our job isn't just to spot the issue, it's to work with you to find a solution that fits your business, while keeping your fire systems compliant and reliable.

That's what a proactive fire protection partnership looks like.

Employee of the Month: Matt SchrammMatt's been recognised this month for his work as Passive Fire & Damper Supervisor.Th...
31/07/2026

Employee of the Month: Matt Schramm

Matt's been recognised this month for his work as Passive Fire & Damper Supervisor.

The standard he holds on site, how he's managed recent projects and the trust the team places in him - that's what consistent, reliable work looks like.

Thanks for setting the bar, Matt.

Address

Unit 29/19 McCauley Street
Matraville, NSW
2036

Opening Hours

Monday 8am - 5pm
Tuesday 8am - 5pm
Wednesday 8am - 5pm
Thursday 8am - 5pm
Friday 8am - 5pm

Telephone

+611300340210

Alerts

Be the first to know and let us send you an email when 2020 Fire Protection posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Business

Send a message to 2020 Fire Protection:

Shortcuts

Share