16 batt- 192 vdc control card setting
24/02/2025

16 batt- 192 vdc control card setting

20 batt - 240 vdc control card settings
24/02/2025

20 batt - 240 vdc control card settings

24/11/2024

INPUT MCB RATING FOR UPS:

10kVA , 20kVA : 63A
30kVA , 40kVA : 100A
50kVA: 160A
60kVA : 160A
80kVA : 200A
100kVA : 250A
120kVA: 250A

@@@@@@@@@@@@@@

INPUT & Output Cable Size: must be Copper with ring type lug

10kVA : 4 sq. Mm
20kVA : 6 sq.mm.
30kVA : 10 sq. Mm.
40kVA: 16 sq mm.
50kVA : 25 sq. Mm.
60kVA : 35 sq. Mm.
80kVA : 35 sq. Mm.
100kVA : 50 sq. Mm.
120kVA: 50 sq. Mm.

22/11/2024

Battery clubbing -3kva ups

Kstar/UTL Kesara fault code
29/01/2024

Kstar/UTL Kesara fault code

Common battery bank with two UPS -Dc links interconnection
05/02/2023

Common battery bank with two UPS -Dc links interconnection

13/12/2022
03/11/2022

Good Day
192V ke DI me battery connection kaise karna hai uske liye please ye chota sa video dekh len. Thankyou.

14/07/2020

Outdoor three phase servo Stebiliser..

Cable size and current capacity