23/08/2026
⚡ Transformer Routine Testing — Part 1/5
Insulation Resistance (Megger)
I’m starting a short series on routine transformer testing — not just what each test is called, but what is actually happening electrically, what I look for in the results, and what those numbers can tell us when something isn’t right.
During my time in transformer testing, I carried out routine, type and special tests on oil-filled transformers ranging from 25 kVA up to 5000 kVA, including 11 kV/433 V, 22 kV/415 V and 33 kV/480 V units.
Let’s start with one of the first checks:
Insulation Resistance
For this test, I normally applied:
⚡ 2.5 kV DC
⏱️ 60 seconds
And checked three insulation paths:
• HV → Earth
• LV → Earth
• HV → LV
All terminals of the winding under test were shorted together. For a star-connected LV winding, the neutral was included as well.
🛡️ One part of this test that doesn’t get discussed much is the GUARD terminal.
→ HV to Earth: LV connected to GUARD
→ LV to Earth: HV connected to GUARD
→ HV to LV: transformer tank connected to GUARD
Why?
Because we want to exclude unwanted parallel leakage paths and measure the insulation path we are actually interested in.
⚙️ Electrically, the Megger is doing something quite simple:
DC Voltage → Very Small Current → Resistance
R = V / I
With healthy transformer insulation, the measured current can be down in the microamp range or even into nanoamps, which is why the resistance can easily reach GΩ.
But this is where it gets more interesting.
When 2.5 kV DC is first applied, the current is not purely leakage current.
Initially, we also have:
🔹 Capacitive charging current
🔹 Dielectric absorption / polarization current
🔹 Leakage / conduction current
The charging and absorption components reduce with time.
That is one reason why the defined 60-second reading is more meaningful than simply looking at the first number that appears after pressing TEST.
📈 On new transformers, we normally expected the results to be comfortably in the GΩ range and depends upon Transformer construction, temperature, insulation condition, contamination and measurement configuration.
⚡ Small test-bay fact:
We may be applying 2.5 kV, while healthy insulation is only passing micro or nanoamps. If someone accidentally becomes part of the circuit, the current can rise rapidly towards the tester’s current limit and the unit may cut out at 3mA.
Still… definitely not something I’d recommend testing personally. 😄⚡
The real engineering is understanding:
• What current are we actually measuring?
• Which insulation path are we testing?
• Why does the resistance change with time?
• And does the result make sense for that transformer and test configuration?