Calibrated certificate📄

11/10/2026

SITE INSPECTION REPORT
Date: Oct 10, 2026
09754201224
viber same number.


1.0 PURPOSE
Site inspection was conducted for a walk-in client for Water Heater
installation. Upon checking, there was NO AVAILABLE SLOT in the existing
Panel Board.

Client was advised to conduct electrical check-up first:
1. Load Schedule
2. Full Load Test
3. Evaluation & Recommendations

2.0 FINDINGS

2.1 CRITICAL: DOUBLE TAPPING AT MAIN SERVICE
Location: Main Meralco Service Side
Finding: 2.5HP Aircon is directly tapped at the main line.
Issue: Even with Main TQC Breaker OFF, the Aircon remains ENERGIZED.
Remark: Improper and unsafe installation. Bypasses main protection.

2.2 PANEL BOARD CAPACITY
Finding: No available space for additional breaker for Water Heater.

2.3 FULL LOAD TEST RESULT
After correction of double tapping, full load test was conducted.
Result: 42 AMPERES total load.

2.4 CRITICAL: WIRE & BREAKER MISMATCH
Feeder Wire: #8.0 AWG
Main Breaker: 60A 2-Pole
Remark: #8.0 AWG is rated for 40A-50A only. Using 60A breaker is
unsafe and can cause wire overheating and fire.

2.5 CRITICAL: IMPROPER BRANCH CIRCUIT
Finding: 30A breakers used in branches.
Issue: Continuous Load and Special Purpose Outlet for Heating Element
are combined in one circuit.
Remark: Heating loads must have dedicated circuit. 30A is too high
for branch wiring.

3.0 HAZARD WARNING
âš  ELECTRICAL SHOCK & FIRE HAZARD due to double tapping.
âš  OVERHEATING & FIRE HAZARD due to undersized wire with oversized breaker.
âš  CIRCUIT OVERLOAD due to combined heating and continuous loads.

4.0 RECOMMENDATIONS
1. Upgrade panel board or add sub-panel for additional circuits.
2. Remove double tapping. All loads must pass through Main Breaker.
3. Upgrade feeder wire to #6.0 AWG THHN to match 60A breaker,
OR downgrade breaker to 40A to match #8.0 wire.
4. Provide dedicated circuit for Water Heater and other heating loads.
5. Prepare proper Load Schedule per Philippine Electrical Code.

5.0 CONCLUSION
Water Heater installation is ON HOLD until all electrical hazards are
corrected. Immediate action is recommended.

Prepared by:
Mark Geralfel cabilin
Head electrician

EV CHARGER INSTALLATION SERVICESWITH SMART WIFI MONITORING SYSTEM09754201224viber same number.Services Offered:- Full El...
28/09/2026

EV CHARGER INSTALLATION SERVICES
WITH SMART WIFI MONITORING SYSTEM

09754201224
viber same number.

Services Offered:
- Full Electrical Installation for EV Charger
- Standard Wiring using PHELPS DODGE WIRE
- With Complete GROUNDING SYSTEM for Safety
- Panel Setup with RCCB, SPD, Digital Meter & Voltage Protection
- WIFI CONNECTED MONITORING SYSTEM

conduct insulation resistance test megger tester.
with calibration certificate updated.
legal testing commissioning.

What's Included:
- CNC 40A RCCB with Leakage Protection
- Multi-Function Digital Meter - Volts, Amps, Watts, KWH
- Auto Voltage Protector
- CNC Surge Protective Device SPD
- Heat Extinguishing Device
- WIFI MONITOR - Real-time monitoring kahit malayo
Makikita ang Voltage, Current, Amper
Makikita kung umiinit ang wire/system
Real-time status ng electrical system mo

Perfect for: Home, Condo, Parking, Office, Commercial
Monitor your EV Charger anytime, anywhere using your phone.

We also accept nearby areas.
Standard materials and safety standards followed.

Price: PM FOR QUOTATION
Message me for details and site visit.

PM LANG SA INTERESADO.

SUBJECT: Service Report - Final Corrective Action & Recommendation -  Bldg 268Date:September 2, 2026  Location: Bldg 268...
18/09/2026

SUBJECT: Service Report - Final Corrective Action & Recommendation - Bldg 268
Date:September 2, 2026
Location: Bldg 268

Good day Sir/Ma'am,

This is to report the final corrective actions performed and recommendations for the electrical system.

1. ACTION TAKEN

A. Finding: Loose connections were found.
All connections were properly retightened. The Compression Tap Connector was re-installed and sealed with rubber tape and electrical tape.

B. Load Side Busbar Correction
1. Upon re-inspection of the load side busbar gutter, we found that it was re-opened by another contractor after our initial retightening.
2. Finding: Due to this, 1 bolt was found with lost thread and had become loose again.
3. Action: We provided and installed a new vault with nuts to replace the damaged hardware. All busbar connections were retightened and secured.

C. Insulation Resistance Test - To All Tenant Feeders

1. Conducted IR Test from the main breakers going to
all tenant units.
2. Result: PASSED. All tenant feeders passed the Insulation Resistance Test. All systems are good and operational.

2. CRITICAL FINDING & URGENT RECOMMENDATION
The entire electrical system on the exterior is still exposed to rain and the elements.
As of now, the system is energized. However, it is NOT TOTALLY SAFE until proper weatherproofing is installed.

Recommended Immediate Action:
1. Installation of Water Tight Hub / Waterproofing
The panel entries and conduits must be provided with Water Tight Hubs and properly concealed to prevent water ingress. This is urgent to avoid future damage and safety hazards.
2. Concealment of Electrical System
We recommend to study and implement the proper concealment of the entire exterior electrical system for long-term protection.

3. RECOMMENDATION: PMS FOR ALL TENANT UNITS
To ensure safety per unit, we recommend the implementation of *Preventive Maintenance Schedule (PMS) for ALL TENANT UNITS.

PMS Scope per Tenant Unit:
1. Insulation Resistance Test
2. Thermal Scanning Test
3. Full Load Test / Load Balancing Test

Deliverable:After the PMS, each tenant will be issued their own Evaluation Report with test results.
Note:The witness and contractor for the PMS will be coordinated by the Admin/Management. Our role is to recommend the testing for safety compliance.

4. CONCLUSION
All corrective actions on the line side and load side have been completed and the system is currently operational. However, due to exposure to rain, the installation of
Water Tight Hubs and proper concealment is URGENT to ensure long-term safety and reliability. The recommended PMS for tenants is also advised to address unit-level issues.

Thank you,

📊 PROFESSIONAL THERMAL SCANNING SERVICES + FREE TRAINING 📊09754201224 viber same number🫡Prevent electrical failures befo...
09/09/2026

📊 PROFESSIONAL THERMAL SCANNING SERVICES + FREE TRAINING 📊

09754201224 viber same number🫡

Prevent electrical failures before they happen!

offers Thermal Scanning using Certified Level 1 & Level 2 Thermographers.

OUR SERVICES:
✓ Infrared Thermal Scanning Test
✓ Professional Thermal Report with Thermal + Visual Images
✓ Temperature Analysis, ΔT Comparison & Priority Recommendations
✓ On-site Testing using our own equipment

FREE BONUS:
✓ Technical Training for your team
✓ Available Online or On-site the day after testing
✓ Learn proper scanning techniques and how to equipment works and operates

WHY THERMAL SCANNING?
- Detect loose connections, overloads localized heating & harmonics
- Prevent downtime and electrical failures
- Safety of the equipment and facilities

at Arkray Industry West, Inc., Cavite Economic Zone Dr, Rosario, Cavitesuccessfully conducted for an insulation resistan...
24/08/2026

at Arkray Industry West, Inc., Cavite Economic Zone Dr, Rosario, Cavite

successfully conducted for an insulation resistance test ( Megger brand tester )

for more inquiry 09754201224 viber same numner.

Address

Manila

Telephone

+639754201224

Website