🔥 FIRE DOOR SAFETY WEEK 🔥
Are you aware of what you Fire Door Specifications should be?
🚪 FIRE DOOR THICKNESS:
Fire resisting - means designated to resist the passage of flame and smoke, and provide insulation as defined under the prescribed conditions of test appropriate to such condition in accordance with BS 476-22:1987 or BS EN 1634-1:2008.
- 30 Minute fire resisting doors (FD30) - should generally be no less than 44mm in thickness
- 60 Minute fire resisting doors (FD60) - should generally be no less than 54mm in thickness
🚪 SELF-CLOSING DEVICES:
Where self-closing devices are specified - standard overhead units should be used, meeting BS EN 1154 (Building hardware - Controlled door closing devices).
Older closers - may be tested to BS 6459-1 and it is recommended these are replaced. The strength and features of the control must be correct for the size and use of the door fitted.
🚪 HINGES:
Hinges should be tested as part of the overall fire doorset. Where a door assembly requires replacement any replacement hinges should be certified for use in the relevant door assembly configuration (timber/timber, timber/metal, metal/metal etc.). Refer to BS EN 1935:2002 (Building hardware - Single-axis hinges). Where a door is subject to repair as a result of this report, it is recommended the hinges are confirmed to be fitted with intumescent pads as part of the works.
🚪 SEALS:
In addition to intumescent strips, which are standard on most fire doors, cold smoke seals may also be installed/required. In general, all fire doors leading onto means of escape (such as protected corridors, stair-cores and protected lobbies) should be fitted with cold smoke seals. Regular checks should be carried out to ensure cold smoke seals are in good condition and make contact with the door/frame at all points. it may become apparent that doors which are used frequently have damaged seals on a regular basis and should be replaced at the earliest opportunity.
When was your last fire door inspection?
📞 Get in touch with Howard Fire Inspections Ltd to arrange a fire door inspection or a Fire Risk Assessment.
🌐